| Supply
::::::::
Power
Transformers
|
| |
| Completely
Self-Protected Transformers (CRGO Silicon
Steel / Amorphous Metal) |
 |
VE’s
Completely Self Protected Transformers
(CSP) offer a complete and safe solution
against lightening, switch surges and
severe secondary overloads. |
|
|
-
Higher Transformer
Availability: Available for a longer
duration than conventional transformers.
Internal breaker (Type CLR) is tripped
by a standard Bi-Metallic thermal
trip element, which integrates oil
temperature and secondary current
flow, allowing the transformer to
continue to operate even under overload
conditions, until the oil temperature
makes coil damage imminent. Improvised
CQR Type breakers can also be provided
which are furnished with instantaneous
magnetic trip element in addition
to the Bi- Metallic thermal trip element.
-
More Reliable
Service: CSP transformers efficiently
and effectively disconnect the load
from the transformer under overload
conditions. Moreover CSP components
help in identifying locations where
improvements in load management may
be necessary.
-
Lower System Cost
: Considering the operating costs
of energy supply and replacement cost
of the transformers that have failed
prematurely due to overload, CSP transformers
would no doubt fair better than conventional
ones.
-
Easier and Simpler
Installation: Involves only one piece
of electrical equipment, the transformer
and only one high voltage electrical
connection to the distribution line.
-
Safer operation.
|
|
|
|
-
Terminal Connectors
-
Pressure Relief Device
/ Explosion Vent
-
Cable Box
-
Rollers (Uni-Directional
/ Bi-Directional)
-
Arcing Horns
-
Free Breathing /
Hermetically Sealed
-
Cable Terminations
|
|
| Ratings |
: |
Single Phase: CRGO:
Upto 167 kVA
AMT: Upto 167 kVA
Three Phase: CRGO: Upto 315 kVA
AMT: Upto 315 kVA |
| Number of Phases |
: |
Single Phase and Three Phase |
| Applicable Standards |
: |
IS, IEC, ANSI, JIS, BS etc. |
| Cooling |
: |
ONAN, OA |
| Insulating Fluid |
: |
Mineral Oil to Specification |
| Frequency |
: |
50 Hz, 60 Hz |
| Vector Group |
: |
As specified |
| Primary Voltage |
: |
Upto 11 kV |
| Secondary Voltage |
: |
415, 433 V (Other voltages as required) |
| Winding Material |
: |
Copper / Aluminium |
| Tapping Range |
: |
±5% in steps of 2.5%(Other
tappings as required) |
| Impedance |
: |
In line with applicable standards
|
|
|
|